Under the 2026 NEC, solar PV systems need a rapid shutdown label, marked PV dc circuits, a "PV SYSTEM DISCONNECT" label on each PV system disconnect, and a power source plaque, label or directory. Those requirements are in 690.12(D), 690.31(D)(2), 690.13(C) and 705.10.
*Covers the 2026 NEC. Checked November 2026. Written by Panel Label Company in Clayton, NC. Our founder spent 13 years in commercial construction as a project manager and superintendent.*
Your inspector enforces the edition your state or city has adopted. Older editions can use different section numbers and wording, so confirm with your AHJ before ordering. See NEC adoption by state.
Rapid Shutdown Labels (2026 NEC 690.12(D))
Buildings with PV systems need a permanent label at each service equipment location the PV systems connect to, or at an approved readily visible location. The label has to:
- Show the location of the rapid shutdown initiation devices
- Include a simple diagram of a building with a roof
- Include this wording: SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN. TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY.
- Use capital letters at least 3/8" high for "SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN," with all text legible and contrasting with the background
If a building has more than one rapid shutdown type, or PV systems with no rapid shutdown, 690.12(D)(1) calls for a detailed plan view diagram of the roof. It shows each different PV system, with a dotted line around areas that remain energized after rapid shutdown is initiated.
The rapid shutdown switch gets its own label, on the switch or no more than 3 ft from it, with the wording RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM. Under 690.12(D)(2), that label has to be reflective, with all capital letters at least 3/8" high, in white on a red background.
You may see the rapid shutdown label cited as 690.56(C). In the 2026 NEC, 690.56 only says that plaques or directories follow 705.10. If your job is under an older edition, check that edition's section and wording.
A paper sticker printed on an office printer will not hold up on an outdoor disconnect through a Carolina summer, so choose a material suited to where the label lives.
PV DC Circuit Marking (2026 NEC 690.31(D)(2))
For PV system dc circuits on or in buildings, unless the location and arrangement make the purpose evident, these have to be marked PHOTOVOLTAIC POWER SOURCE or SOLAR PV DC CIRCUIT:
- Exposed raceways, cable trays and other wiring methods
- Covers or enclosures of pull boxes and junction boxes
- Conduit bodies with any unused conduit openings
The marking has to be a permanently affixed label or other approved permanent marking, visible after installation, in capital letters at least 3/8" high, white on a red background. Labels have to appear on every section of the wiring system separated by enclosures, walls, partitions, ceilings or floors, with no more than 10 ft between labels or markings, or between a label and a marking. They also have to be suitable for the environment where they are installed.
Disconnect Marking (2026 NEC 690.13(C), 690.15 and 705.20(F))
Each PV system disconnecting means has to be permanently marked "PV SYSTEM DISCONNECT" or equivalent under 690.13(C).
690.15 covers disconnecting means for isolating PV equipment, such as ac PV modules, fuses, dc-to-dc converters, inverters and charge controllers. Two markings can apply:
- An isolating device not rated to interrupt the circuit current has to be marked "Do Not Disconnect Under Load" or "Not for Current Interrupting."
- Equipment disconnecting means, other than those complying with 690.33, have to carry the 705.20(F) warning if the line and load terminals can be energized in the open position. The wording, or equivalent, is: WARNING ELECTRIC SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION.
Our engraved electrical labels and equipment nameplates cover fixed wording like this.
Power Source Plaques, Labels and Directories (2026 NEC 705.10)
705.10 calls for permanent plaques, labels or directories at each service equipment location, or at an approved readily visible location. They have to:
- Denote the location of each power source disconnecting means for the building or structure
- Show the emergency telephone numbers of any off-site entities servicing the power source systems
- Be marked with the wording CAUTION: MULTIPLE SOURCES OF POWER
Installations with multiple colocated power production sources can be identified as a group, so the plaque doesn't have to identify each source individually.
What Goes Where on a Typical Job
| Location | Required marking | Material to consider |
|---|---|---|
| Service equipment or approved visible location | Rapid shutdown label, 690.12(D) | UV stable vinyl or engraved acrylic |
| On or within 3 ft of the rapid shutdown switch | RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM, 690.12(D)(2) | Reflective white on red |
| Each PV system disconnect | PV SYSTEM DISCONNECT or equivalent, 690.13(C) | Engraved two ply acrylic |
| Disconnects with both sides energized when open | Line and load warning, 705.20(F) | Engraved two ply acrylic |
| PV dc raceways, cable trays, box covers and enclosures | PHOTOVOLTAIC POWER SOURCE or SOLAR PV DC CIRCUIT, 690.31(D)(2) | White on red engraved acrylic or industrial vinyl |
| Service equipment or approved visible location | CAUTION: MULTIPLE SOURCES OF POWER with disconnect locations, 705.10 | Engraved acrylic |
See our solar PV labels. If the job includes charging equipment, see our EVSE disconnect labels.
Why Engraved and Vinyl Labels Both Have a Place Here
Labels that live outdoors in direct sun need materials suitable for the environment. Rowmark rates DurMark colorfast for 2+ years in reasonable outdoor conditions. A properly rated printed vinyl is another option, not a laser printed sticker.
Engraved wins where the marking is permanent equipment identification. The text is cut through the cap layer of the material, so there is no printed surface to peel or wear off. Our plates run on UL approved Rowmark DurMark two ply acrylic in seven standard color combinations, including the red and white you need for PV warning wording. See engraved industrial nameplates for the material detail.
Printed vinyl wins where you need a full color ANSI Z535.4 formatted hazard message with a signal word header, or a large placard on a curved or awkward surface. Our vinyl safety labels print on 3.0 mil industrial vinyl with a UV stable overlaminate, rated 5+ years outdoors, at $4.60 each with no minimum. For the specific voltage callouts that show up on PV service equipment, see voltage labels and high voltage labels.
Getting the Wording Right Before You Order
Two things sink solar labeling jobs: wording that does not match the code section, and material that does not last. This post covers the 2026 NEC, so if your AHJ has adopted another edition, match your wording to that edition and confirm with the inspector on any label you are unsure about. Then match the material to where the label lives.
You can type your wording and see a live preview with real sizing in our label designer. Engraved plates start at $5.10, vinyl safety labels at $4.60, both with no minimum order and 1 to 2 business day production out of Clayton, NC.
Sources
- NFPA 70, National Electrical Code, 2026 edition: Sections 690.12(D), 690.13(C), 690.15, 690.31(D)(2), 690.56, 705.10 and 705.20(F)