We have written about NEC 110.21 field-applied labeling and NEC 110.24 available fault current marking separately. NEC 110.22 is the third piece of that cluster, and it is the one most often confused with the other two, because all three deal with labels on or near overcurrent protective devices. Here is what 110.22 actually requires, and how it differs from its neighbors.
What NEC 110.22 Covers
NEC 110.22 addresses the identification of disconnecting means and, critically, the labeling required when equipment is applied as part of a series combination rating. The section breaks into three parts.
110.22(A) - General disconnect identification. Every disconnecting means for motors, appliances and other equipment must be legibly marked to identify its purpose, unless the purpose is evident from the installation. That sounds simple, but on a crowded gear lineup with a dozen disconnects, "evident" is doing a lot of work. It is the reason inspectors push back on generic markings like "Disconnect 1" with no equipment reference. The marking has to tell the next person what the switch actually controls: AHU-3 SUPPLY FAN, not SWITCH 4. Outside one- and two-family dwellings, the marking also has to identify the circuit source that supplies the disconnecting means, unless that is evident. The 2026 NEC adds its location.
110.22(B) - Engineered series combination systems. Where circuit breakers or fuses are applied in an engineered series combination system, the equipment enclosures require a field marking that reads: CAUTION - ENGINEERED SERIES COMBINATION SYSTEM RATED _____ AMPERES. IDENTIFIED REPLACEMENT COMPONENTS REQUIRED.
110.22(C) - Tested series combination systems. Where circuit breakers or fuses are applied as part of a tested series combination system, meaning they are protected by an upstream device so the downstream device can be applied above its own individual interrupting rating, the equipment enclosures require a field marking that reads: CAUTION - SERIES COMBINATION SYSTEM RATED _____ AMPERES. IDENTIFIED REPLACEMENT COMPONENTS REQUIRED.
The Exact Caution Wording
The NEC is prescriptive about what the series combination labels have to communicate. The code-referenced wording reads:
- 110.22(B), engineered: CAUTION - ENGINEERED SERIES COMBINATION SYSTEM RATED _____ AMPERES. IDENTIFIED REPLACEMENT COMPONENTS REQUIRED.
- 110.22(C), tested: CAUTION - SERIES COMBINATION SYSTEM RATED _____ AMPERES. IDENTIFIED REPLACEMENT COMPONENTS REQUIRED.
Two details trip people up. First, the blank is not optional. It gets the tested short-circuit current rating of the combination in amperes, taken from the manufacturer's series rating tables, not the interrupting rating stamped on the individual breaker. Second, the label has to be durable enough for the environment under 110.21(B), which is why a handwritten placard or an office-printed sticker inside a switchgear cabinet gets flagged.
Typical finished wording on a plate for a tested combination looks like this:
- CAUTION - SERIES COMBINATION SYSTEM RATED 65,000 AMPERES. IDENTIFIED REPLACEMENT COMPONENTS REQUIRED.
Yellow with black text is the conventional choice for a CAUTION signal word under ANSI Z535, and it is the combination most panel shops order for these.
Why the Series Rating Label Matters More Than It Looks
The series combination label is not a formality. Series ratings only work with the exact combination of devices that were tested and listed together. If a breaker or fuse gets swapped for an equivalent-looking device from another manufacturer, or a different model years down the road, the series rating can be silently invalidated and the equipment may no longer be able to safely interrupt the fault current it is exposed to.
The label is the only thing standing between a future electrician and the assumption that any compatible-looking breaker will do. That is why the marking should reference enough information, or point clearly to the panel documentation, that someone doing future work can verify compatibility before making a change.
How 110.22 Fits With 110.21 and 110.24
| Code Section | What It Requires | Typical Label Content |
|---|---|---|
| NEC 110.21 | Field-applied markings must be legible and durable for the environment | Hazard wording, durable field marking |
| NEC 110.22 | Disconnect purpose identification and series combination caution | Equipment purpose, series rating amperes, replacement caution |
| NEC 110.24 | Available fault current marking on service equipment | Calculated fault current value and calculation date |
These three sections routinely produce multiple labels on or near the same equipment. Panel shops often order all three as one coordinated set rather than piecemeal, which keeps terminology and format consistent and avoids adjacent labels that contradict each other.
Getting the Label Right
Because the 110.22(B) and 110.22(C) caution statements are prescriptive about what it must communicate, not just that the system is series rated but the warning about future component replacement, it is worth using a plate with the full caution language engraved in rather than a generic "series rated" sticker.
Engraved two-ply acrylic holds up at the panel because the text is cut through the cap layer into the material, so there is no printed surface to peel or wear off. Our plates run on UL approved Rowmark DurMark material in seven standard color combinations, including the black on yellow used for CAUTION wording. See engraved industrial nameplates for the material detail, or engraved electrical labels for the disconnect and equipment identification side of 110.22(A).
You can type your exact wording, including the amperes value, and see a live preview with real sizing in our label designer. Engraved plates start at $5.10, with no minimum order and 1 to 2 business day production out of Clayton, NC.